Provides a visual display of its last sampled reading and current operating state.
Last Sampled Reading
Normal Reading: CLOS (closed)
Out of Range Reading (Alarm state): OPEN
Current operating state indicators
Segment |
Description |
---|---|
Signal OK |
Indicates its last connection to the facility's network and check-in to OneVue was successful. |
No Signal |
Indicates the device could not establish a connection to the facility's network and check-in to OneVue. For wireless network use, this may be due to the device is not within range of a wireless access point or the wireless signal strength is not adequate for normal operation. If the device is powered by AC or Power over Ethernet (PoE), the yellow LED indicator also flashes during this state. |
Err (Temperature or Water Leak Sensor) |
For a temperature sensor: indicates either of the following: (1) a probe is either removed from or not inserted correctly into the sensor's probe input jack, or can be caused due to the probe is not operating as expected, or (2) the collection period must be reset, which may result from inserting a new probe or reinserting a probe. To clear the error state and reset the Lo/Hi collection period, verify the probe is inserted into the sensor jack and press and release the sensor Silence (bell) button . For a water leak sensor: indicates the water detector is either removed from or not inserted correctly into the sensor's input jack or can be caused due to the detector is not operating as expected. During this error:
|
Low Battery icon |
Indicates an Alarm state due to its estimated battery life is less than 25%. To avoid loss of battery power, be sure to replace its batteries. Requires 2 AA Lithium AA batteries. The use of alkaline batteries is not recommended. |
Lbat |
Indicates an Alarm state due to its battery level is critically low. Replace its batteries immediately. Requires 2 AA Lithium AA batteries. The use of alkaline batteries is not recommended. Readings are not displayed, sampled, logged, or transmitted to OneVue during this state. |
Up |
Indicates a firmware update is currently being applied to the device. Do not remove power during this state. When the firmware update is complete, UP is no longer displayed. Readings are not displayed, sampled, logged, or transmitted to OneVue during this state. |
Con |
The device is in configuration mode. The config icon is also displayed. Data is not logged or transmitted to OneVue during this state. |
H \ / F (HwF) |
Indicates an internal hardware failure. This is due to the main processor cannot communicate with the internal sensing element. Contact Primex Technical Support for assistance. Readings are not displayed, sampled, logged, or transmitted to OneVue during this state. |
FTST |
Indicates the sensor is in a Factory Test Mode state. A sensor enters Factory Test Mode when its Silence button (bell button) is pressed and held for more than 7 seconds. This mode does not impact the use of the sensor or the logged readings stored in its local memory. The purpose of this mode is for use by Primex during factory testing. When a sensor has entered this mode, it performs a factory test and power-cycles (turns off and on), which can take up to approximately 1 minute. Once the factory test is complete, the sensor returns to its normal operating mode. Readings are not displayed, sampled, logged, or transmitted to OneVue during this state. |
A sensor has two service buttons located on the front of the device.
A Primex sensor has three LED indicators (green, yellow, and red) that provide a visual indicator of its current state.
LED |
State/Status |
Device power |
---|---|---|
Green LED illuminated |
Normal state Operating as expected |
AC or PoE power: LED illuminated Battery-power only: LED disabled to conserve battery life. Upon power up, illuminates for 2 seconds |
Yellow LED flashing |
Warning/Alarm state due to either of the below conditions:
|
AC or PoE power: LED is illuminated and flashing Refer to the LCD display to identify the condition |
Red LED flashing |
Reading Alarm (Out of Range, Past Alarm Delay status)
|
All power methods: LED is illuminated and flashing |